|
ASHRAE 62.1 Standard adopted by International Code Council |
|
|
|
|
Tuesday, 05 June 2007 |
The
International Code Council approved recently an ASHRAE
proposal to incorporate the prescriptive ventilation rate procedure from
ANSI/ASHRAE Standard 62.1-2004, Ventilation for Acceptable Indoor Air
Quality, in the IMC. The code establishes minimum regulations adopted and
implemented by federal, state and local government agencies for mechanical
systems in new buildings and will be included in the 2007 IMC supplement,
reveals the organizations press release.
The current ventilation criteria in the IMC are based on ASHRAE Standard
62-1989. After 20 years of IAQ research and experience with ventilation system
design, ASHRAE introduced an improved version of the standard in 2004 to
include the new rates and calculation procedures, and has recently published a
new edition that includes requirements for the separation of areas with
environmental tobacco smoke (ETS) from areas without ETS in the same building,
as well as clarification of how designers must analyze mechanical cooling
systems to help limit space relative humidity.
With
adoption of the new calculation procedures, we can expect to see improved
indoor air quality in many previously under-ventilated multiple-zone systems,
said Dennis
Stanke, chair of the 62.1 committee. Ventilation systems with lower outdoor
rates compared to the current code reduce both first costs and energy costs,
while system designs that account properly for air distribution within
buildings result in better indoor air quality than designs based on
over-simplified air distribution assumptions.
|